Schaffner Siemens Drive

6SL3210-1KE32-4AF1

Select Category

AC line reactor

RWK 212-280-KS
max. 500 VAC 50/60 Hz, 0.1 mH, 280 A
RWK 212-330-KS
max. 500 VAC 50/60 Hz, 0.09 mH, 330 A

Passive harmonic filter

50 Hz

FN 3410-260-99
380-500 VAC, rated load power 132 kW @400 VAC 160 kW @500 VAC, 5% THID
FN 3410-320-99
380-500 VAC, rated load power 160 kW @400 VAC 200 kW @500 VAC, 5% THID
FN 3416-260-99
380-500 VAC, rated load power 132 kW @400 VAC, 160 kW @500 VAC, 10% THID with Ldc, 15% THID without Ldc
FN 3416-320-99
380-500 VAC, rated load power 160 kW @400 VAC, 200 kW @500 VAC, 10% THID with Ldc, 15% THID without Ldc
FN 3440-132-118-E0FAJXX
380-415 VAC, rated load power 132 kW @400 VAC, 5% THID, modular configurable
FN 3440-160-118-E0FAJXX
380-415 VAC, rated load power 160 kW @400 VAC, 5% THID, modular configurable
FN 3450-132-118-E0FAJRX
440-500 VAC, rated load power 132 kW @480 VAC, 5% THID, modular configurable
FN 3450-160-118-E0FAJXX
440-500 VAC, rated load power 160 kW @480 VAC, 5% THID, modular configurable

60 Hz

FN 3412-240-99
380-480 VAC, rated load power 200 HP @460 VAC, 5% THID
FN 3412-310-99
380-480 VAC, rated load power 250 HP @460 VAC, 5% THID
FN 3418-240-99
380-480 VAC, rated load power 200 HP @460 VAC, 10% THID with Ldc, 15% THID without Ldc
FN 3418-310-99
380-480 VAC, rated load power 250 HP @460 VAC, 10% THID with Ldc, 15% THID without Ldc
FN 3452-200-118-E0FAJRX
440-480 VAC, rated load power 200 HP @480 VAC, 5% THID, modular configurable
FN 3452-250-118-E0FAJXX
440-480 VAC, rated load power 250 HP @480 VAC, 5% THID, modular configurable

Output filter

dv/dt filter

FN 5060-250-99
rated current 250 A @40°C/50 Hz, L=0.031 mH, C=68 nF
FN 5060-320-99
rated current 320 A @40°C/50 Hz, L=0.024 mH, C=68 nF

Sine-wave filter

FN 5040-260-99
rated current 260 A @45°C/50 Hz, minimum switching frequency 3 kHz, max motor cable length 1000 m
FN 5040-410-99
rated current 410 A @45°C/50 Hz, minimum switching frequency 3 kHz, max. motor cable length 1500 m

EMC filter

Motor cable length ≤50 m class C1

FN 3359-250-28
max. 520 VAC up to 60 Hz, rated current 250 A @50°C, IP 20

Motor cable lenght ≤50 m class C2

FN 3359-250-28
max. 520 VAC up to 60 Hz, rated current 250 A @50°C, IP 20

Motor cable length >50 m class C1

FN 3120 H-230-40
max. 520 VAC up to 60 Hz, rated current 230 A @50°C, IP 20

Motor cable lenght >50 m class C2

FN 3120 H-230-40
max. 520 VAC up to 60 Hz, rated current 230 A @50°C, IP 20

For IT power networks class C2

FN 3359 HV-250-28
max. 690 VAC up to 60 Hz, rated current 250 A @50°C, IP 20

3-phase with neutral for machine tools and low leakage current applications

FN 3280 H-300-99
max. 520 VAC up to 60 Hz, rated current 300 A @50°C, IP 00



Remarks Low Leakage applications
All capacitors to earth (referred to as Y capacitors) in the internal EMC filters of the motor drive should be interrupted, as these capacitors can generate additional leakage currents. Drives with built-in EMC filters are not recommended e.g. with low leakage filters.

Remarks EMC/EMI Filters:
All suggested Schaffner products are recommendations. The final suitability can be guaranteed only by a measurement in the application and is part of the responsibility of the customer. The information of the limit value class C1 or C2 covers only the conducted emission. The Drive Options, which are not produced by SIEMENS itself, nevertheless the manufacturer have a prozessual certification from SIEMENS, no liability is assumed by SIEMENS.

Remarks for 200 V Passive Harmonics and Output Filters:
The final filter suitability can only be guaranteed in terms of a measurement within the application and is part of the responsibility of the customer. All suggested Schaffner products are recommendations only.  Please use the document “Remarks for Schaffner Recommendation List” available in the Tools and Tips section of this page for further information.
Please be aware that dv/dt filters do only work on differential mode.
For those Drive Options that are not produced by SIEMENS itself, but manufacturer has a processual certification of SIEMENS, no liability is assumed by SIEMENS.

Remarks for 400 V Passive Harmonics and Output Filters:
The final filter suitability can only be guaranteed in terms of a measurement within the application and is part of the responsibility of the customer. All suggested Schaffner products are recommendations only.  Please use the document “Remarks for Schaffner Recommendation List” available in the Tools and Tips section of this page for further information.
Ecosine High Power line filters do require motor drives equipped with an 8% (minimum) DC-link choke or the application of a 4% (minimum) AC line choke at the input side of the drive!
Please be aware that dv/dt as well as sine wave filters do only work on differential mode. Dv/dt and sine wave filters ensure compliance with the requirements of IEC60034-17 (general purpose motors) for cable length named in the data sheets (screened/unscreened). Sine wave filters additionally do provide a sinusoidal phase-to-phase motor terminal voltage but have very limited effect on common mode.
For those Drive Options that are not produced by SIEMENS itself, but manufacturer has a processual certification of SIEMENS, no liability is assumed by SIEMENS.

Remarks for 690 V Passive Harmonics and Output Filters:
The final filter suitability can only be guaranteed in terms of a measurement within the application and is part of the responsibility of the customer. All suggested Schaffner products are recommendations only. Please use the document “Remarks for Schaffner Recommendation List” available in the Tools and Tips section of this page for further information.
Ecosine FN 3410 HV filters from 45 kW on do require motor drives equipped with DC-link choke or the application of a 4% (minimum) AC line choke at the input side of the drive!
Please be aware that dv/dt as well as sine wave filters do only work on differential mode. Dv/dt and sine wave filters ensure compliance with the requirements of IEC60034-25B (inverter duty motors) for cable length named in the data sheets (screened/unscreened). Sine wave filters additionally do provide a sinusoidal phase-to-phase motor terminal voltage but have very limited effect on common mode. For the use of general purpose motors on 690V with dv/dt or sine wave filters Schaffner does strongly recommend to contact Schaffner representative prior to any project in order to verify the suitability of the drive-output filter-motor-combination.
For those Drive Options that are not produced by SIEMENS itself, but manufacturer has a processual certification of SIEMENS, no liability is assumed by SIEMENS.